INSTALLATION MANUAL

Installation, battery and fuse sizing, AC safety wiring, CAN ports, LED diagnostics and technical data for the Quick HSI 1204, 1206, 1208, 2404, 2406 and 2408 LR pure sine wave inverters (120 V AC, 60 Hz).

DocumentQuick HSI LR Inverters 1204–2408 Installation & Use Manual
FormatPDF · 48 pages · 3.6 MB
LanguageEnglish
Quick HSI LR Inverters 1204–2408 — Installation & Use Manual

Technical Characteristics (single unit configuration)

HSI 1204 LR HSI 1206 LR HSI 1208 LR HSI 2404 LR HSI 2406 LR HSI 2408 LR
Battery voltage 12 V DC 12 V DC 12 V DC 24 V DC 24 V DC 24 V DC
Nominal output power (1)(2)(3)(6) 410 VA 620 VA 830 VA 410 VA 620 VA 830 VA
Nominal peak load 2s (4)(5)(6) 820 VA 1240 VA 1660 VA 820 VA 1240 VA 1660 VA
Efficiency max. (2)(5)(8) 90% 90% 90% 92% 92% 91%
Input current at nominal power (max.) 43 A 63 A 85 A 21 A 32 A 42 A
Weight 2,6 kg 3,1 kg 3,1 kg 2,6 kg 3,1 kg 3,1 kg
HSI12xx HSI24xx
Nominal input voltage (9) 10,5 ÷ 16 V DC 21 ÷ 32 V DC
Power off / restore, low battery 10,5 ± 0,3 V DC / 12 ± 0,3 V DC 21 ± 0,3 V DC / 24 ± 0,3 V DC
Power off / restore, high battery 16,2 ± 0,3 V DC / 15,3 ± 0,3 V DC 32,3 ± 0,3 V DC / 30,4 ± 0,3 V DC
No-load current ON / LP mode (10) 0,52 A / 0,25 A 0,27 A / 0,13 A
Output disabled / stand-by current (10) 0,17 A / 0,05 A 0,09 A / 0,03 A
  • Output 120 V ac ± 1,5%, 60 Hz ± 0,1%, pure sine THD < 2,5%.
  • Operating temperature –15 ÷ +70 °C (power reduction above 40 °C); humidity max. 95% RH non condensing; aluminium case 170 x 80 x 300 mm; IPX2; CAN bus; EN 62368-1; EN 55032/A – FCC Title 47 Part 15 Subpart B Class A.
  • Notes: (1) at 120 V output; (2) for 11–15 V DC (HSI12xx) or 22–30 V DC (HSI24xx) input; (3) –15 to +40 °C ambient; (4) at 12 / 24 V DC input; (5) resistive load; (6) typical; (8) at 25 °C; (9) power reduced below 11 / 22 V DC or above 15 / 30 V DC; (10) without RDH1660 remote panel. Absolute maximum input 35 V DC.
  • The derating graphs (output vs input voltage and vs ambient temperature) are in the PDF.

Location & Mounting

  • Dry, ventilated area inside the boat, on a level surface without excessive vibration, away from motors and generators and from radio receivers and transmitters.
  • As close to the batteries as possible. At least 5 cm between the inverter (excluding base plate) and walls or objects; do not cover the grilles.
  • Horizontal, or vertical on a bulkhead with the DC terminals facing down (recommended for convection cooling); LEDs visible.
  • Fix with screws able to carry the weight (not supplied). Supplied: inverter, manual, warranty, and RDH1660 remote panel where applicable.
  • Class A product. Power only from a battery, not from a DC power system. Make the AC system to local regulations.

Battery, Cable & Fuse

Model Battery (min.) DC wire (min.) Fuse
HSI 1204 LR 50 Ah 16 mm2 CNL50DIN
HSI 1206 LR 75 Ah 25 mm2 CNL80DIN
HSI 1208 LR 100 Ah 25 mm2 CNL100DIN
HSI 2404 LR 25 Ah 10 mm2 CNL35DIN
HSI 2406 LR 40 Ah 10 mm2 CNL40DIN
HSI 2408 LR 50 Ah 16 mm2 CNL50DIN
  • Maximum battery-to-inverter cable length 3m; size the cable for no more than 0,4V drop at maximum input current.
  • Fuse on the positive, as close to the battery as possible. Terminal torque 4 - 4,5 Nm.
  • An undersized battery or cable makes the inverter cut out or run intermittently.

DC and AC Connection

  1. Main switch to STBY; battery switch OFF.
  2. Positive cable to the + terminal, negative to the – terminal (check polarity: reversal blows the internal fuse and can seriously damage the unit).
  3. AC output cable: yellow/green ground, brown or black 1 phase, blue or black 2 neutral.
  4. AC safety: ground conductor to the boat's centre grounding point; bond the AC output neutral to ground where local rules or a ground-fault detector require; fit a GFCI breaker in the AC output.
  5. Commissioning: check connections and polarity, battery switch ON, main switch ON, test with an AC load.

Never connect the AC output to a generator, shore line, other inverters in parallel or any equipment that can generate power. Decommission in reverse: STBY, battery OFF, verify DC and AC are dead with a voltmeter.

CAN1 / CAN2 Ports (RJ45)

Pin CAN1 CAN2
1 CANL signal CANL signal
2 CANH signal CANH signal
3 Not connected Reserved
4 Simplified inverter status signal (20 mA max) Reserved
5 Inverter negative Reserved
6 Not connected Reserved
7 Inverter positive (100 mA max.) Not connected
8 CAN bus terminator (120 ohm) CAN bus terminator (120 ohm)
  • Pin 4–5 status: high impedance = off, output disabled or a fault interrupting output; 8 V DC (HSI12xx) or 18,5 V DC (HSI24xx) up to input voltage = on (ON or LP) with no fault.
  • The optional RDH1660 remote panel connects here (see its own manual).

Modes

Status LED Mode (switch) Meaning
Steady green On (ON) Running, no problems, full power available
1 short green flash Low power (LP) LP mode, no problems
2 short green flashes Output disabled (ON/LP) Disabled remotely via CAN bus
1 long green flash Stand-by (STBY) Disabled by the main switch
Both LEDs off – No input voltage: check it
  • LP mode: below the LP input level the inverter switches to intermittent output after 20 seconds; above the LP output level it returns to continuous output at once.
  • LP input / output levels (set from the RDH1660): 15/35, 20/40 (factory), 25/45, 30/50, 35/55, 40/60, 45/65 VA.

Diagnostics

LED Fault Action
1 orange Low input voltage (< 10,9 / 21,7 ± 0,3 V DC) Clears above 11,1 / 22,1 ± 0,3 V DC
2 orange Ambient above 40 °C Check location; clears below 40 °C
3 orange High input voltage (> 15,1 / 30,2 ± 0,3 V DC) Clears below 14,9 / 29,8 ± 0,3 V DC
4 orange One fan blocked (power –37%) Clear the blades; else service centre
5 orange Temperature sensor faulty (power –37%) Service centre
Steady orange Two or more of the above See above
6 red Input voltage too low (< 10,5 / 21 ± 0,3 V DC) Clears above 12 / 24 ± 0,3 V DC
7 red Ambient out of limits Clears between –15°C and +40°C
8 red Input voltage too high (> 16,2 / 32,3 ± 0,3 V DC) Clears below 15,3 / 30,4 ± 0,3 V DC
9 red Output short circuit or overload Retries every 30s; check wiring and total load
10 red (error LED) Output overvoltage Service centre
11 red Input fuse blown (probable reversed polarity) Service centre
12 red Both fans jammed Clear the blades; else service centre
13 red Output voltage too low Service centre
14 red Both temperature sensors faulty Service centre
Status + error, very quick red System error Service centre

Values are for HSI12xx / HSI24xx. Faults 10–14 are blocking: switch off, remove the cause, switch on again.

Maintenance

  • No special maintenance. Yearly: check wires and connections are intact and tight (qualified staff), and that the unit is dry, clean and its grilles free of dust.
  • Clean with a soft dry cloth, or a cloth dampened with neutral non-abrasive detergent; do not spill liquids on it.
  • Do not open the case (shock risk); opening by unauthorized personnel voids the warranty. Dimensions A 300 mm (11 13/16 inch), B 170 mm (6 11/16 inch), C 80 mm (3 9/64 inch), D 286,5 mm (11 9/32 inch), E 120 mm (4 23/32 inch).