INSTALLATION MANUAL

Battery and cable sizing (single and parallel), wiring, CAN signals, battery type selection, LEDs, charging stages, fault codes and technical data for the Quick SBC NRG+ High Power chargers: 1100 and 1200 FR (12 V), 1450, 1950 and 2450 HR (24 V).

DocumentQuick SBC NRG+ 1100, 1200, 1450, 1950 & 2450 Battery Chargers Installation & Use Manual
FormatPDF · 32 pages · 1.6 MB
LanguageEnglish
Quick SBC NRG+ 1100, 1200, 1450, 1950 & 2450 Battery Chargers — Installation & Use Manual

Technical Data

SBC 1100 NRG+ FR SBC 1200 NRG+ FR SBC 1450 NRG+ HR SBC 1950 NRG+ HR SBC 2450 NRG+ HR
Battery voltage 12 V 12 V 24 V 24 V 24 V
Maximum output current (1) 80 A 100 A 60 A 80 A 100 A
Max absorption 230/240 Vac (5) 5,4 A 6,5 A 7,5 A 10,1 A 12,5 A
Max absorption 120 Vac (6) 10,6 A 12,7 A – – –
Supply voltage 264 ÷ 83 Vac (reduced under 108 Vac) 264 ÷ 83 Vac 264 ÷ 161 Vac (reduced under 207 Vac) 264 ÷ 161 Vac 264 ÷ 161 Vac
Rated voltage 120-240 120-240 230 - 240 230 - 240 230 - 240
Efficiency (5) ≥ 88% ≥ 88% ≥ 92% ≥ 92% ≥ 92%
Residual ripple (3) < 100 mV RMS < 100 mV RMS < 150 mV RMS < 150 mV RMS < 150 mV RMS
DC drain from batteries (2) < 3,5 mA < 3,5 mA < 5 mA < 5 mA < 5 mA
Battery type Absorption 12 V / 24 V Float 12 V / 24 V
EL open 14,1 / 28,2 Vdc 13,4 / 26,8 Vdc
EL sealed / Gel 14,4 / 28,8 Vdc 13,8 / 27,6 Vdc
AGM 14,4 / 28,8 Vdc 13,6 / 27,2 Vdc
Optima® 14,7 / 29,4 Vdc 13,8 / 27,6 Vdc
Li-Ion 14,2 / 28,4 Vdc 13,5 / 27 Vdc
  • 3 outputs (4) with internal MOSFET separator and output fuses; three-stage IUoU; 45÷66 Hz; power factor 1,00; forced cooling with variable-speed fans.
  • Operating –15 ÷ +70 °C, linear power reduction over +50 °C; humidity max. 95% without condensation; aluminium case 170 x 481 x 81,5 mm; 4,2 kg.
  • Protections: reverse polarity (via fuse), overload, output short circuit, output overvoltage, overheating, battery overtemperature (optional sensors). EN 60335-2-29; EN 55032/A – FCC Title 47 Part 15 Subpart B Class A.
  • Charge compensation with 1 KTBRJ sensor supplied; up to 128 sensors with KTB4 interfaces. Up to three chargers of the same model in parallel for current sharing.
  • (1) Max at normal use or short circuit. (2) No AC, monitor mode off, no LCD. (3) At 50% load, resistive. (4) Each output can give full current; the sum cannot exceed the rating. (5) At 230 Vac and full output. (6) At 120 Vac and full output.

Our store lists these models as "SBC ... Nrg" with the same model numbers and output currents.

Battery & Cable Sizing

Model Battery (single) Output cable 2 in parallel 3 in parallel
SBC 1100 NRG+ FR 360 ÷ 600 Ah 25 mm2 720 ÷ 1200 Ah; J–battery 50 mm2 1080 ÷ 1800 Ah; J–battery 95 mm2
SBC 1200 NRG+ FR 450 ÷ 1000 Ah 35 mm2 900 ÷ 2000 Ah; 95 mm2 1350 ÷ 3000 Ah; 150 mm2
SBC 1450 NRG+ HR 270 ÷ 600 Ah 25 mm2 540 ÷ 1200 Ah; 50 mm2 810 ÷ 1800 Ah; 95 mm2
SBC 1950 NRG+ HR 360 ÷ 800 Ah 35 mm2 720 ÷ 1600 Ah; 70 mm2 1080 ÷ 2400 Ah; 120 mm2
SBC 2450 NRG+ HR 450 ÷ 1000 Ah 35 mm2 900 ÷ 2000 Ah; 95 mm2 1350 ÷ 3000 Ah; 150 mm2
  • Charger-to-junction "J" cable in parallel: same size as the single output cable. 6 cells (12 V) or 12 cells (24 V).
  • Single charger: output wires max 4 meters. Parallel: charger-to-junction cables equal length, never over 2 m; junction to battery under 6 meters.

Location & Supply

  • As close to the batteries as possible, dry and airy; horizontal or vertical with the output connector facing down (vertical preferred). Parallel units side by side.
  • At least 5 cm clearance all round (excluding the base); screws strong enough for the weight.
  • Rechargeable lead (open or sealed), Gel, AGM, Optima® and Li-Ion batteries only.
  • AC cord supplied: brown/black 1 live, blue/black 2 neutral, yellow-green earth. Fit an overvoltage category III switch for on/off; check the rating label matches the mains.
  • Disconnect AC (bipolar switch) and the batteries (isolator) before touching the DC terminals. Batteries gas while charging: ventilate, no sparks or flames. Check polarity: reversal can seriously damage the charger.

Outputs

  • Single: battery positive to an output positive, battery negative to the charger negative, using the supplied connector. With one or two banks always use MASTER (main output) – ideally for the most-used (service) bank. Leave unused outputs free: do not bridge them.
  • Parallel (current sharing): MASTER to junction JM, SLAVE 1 to JS1, SLAVE 2 to JS2, negatives to JCN; each junction to its battery.
  • Current sharing needs at least one RDS 1562 terminal (optional) to set group and priority.
  • Battery temperature sensor KTBRJ on the RJ11 socket (disabled automatically if a KTB4N interface is connected).

CAN IN / CAN OUT (RJ45)

Pin CAN IN CAN OUT
1 CANL CANL
2 CANH CANH
3 Reserved Unconnected
4 Reserved Charger status (≈ +13,5 Vdc / 20 mA max)
5 Reserved Charger negative
6 Reserved Unconnected
7 Unconnected MASTER output voltage (100 mA limited)
8 CAN BUS terminator (120 ohm) CAN BUS terminator (120 ohm)
  • Pin 4 status: high impedance = charger off or manual-reset fault; ≈ + 13,6 Vdc = on, no manual-reset fault.
  • Battery selector (front panel, charger off): 0 EL open (factory), 1 EL sealed, 2 GEL, 3 AGM, 4 Optima®, 5 Li-Ion; 6–9 reserved.

LEDs & Charging

LED State Meaning
STATUS Off / green / orange / red No mains or active error / FLOAT / ABSORPTION / BULK
STATUS Quick / slow flash Power reduction / charge compensation
STATUS Short green pulse / green pulse Monitor mode / stand-by
ERROR Off / flashing / red No problem / manual-reset problem / automatic-reset problem
OUT CURRENT Green, orange, orange, red >2%, >25%, >50%, >75% of max current (flashing in current sharing)
  • BULK: constant current at maximum (or reduced) rating. ABSORPTION: constant voltage until current drops below the ABSORPTION–FLOAT threshold (factory 20% of max current). FLOAT: maintenance voltage.
  • In parallel, IMAX and the threshold are multiplied by the number of chargers (2 or 3).

Fault Codes (ERROR LED flashes)

Flashes Problem Action
1 Output short circuit or overload (auto reset) Check output wiring, battery bank and loads
2 Output fuse open (likely reversed battery polarity) Quick service center
3 Output overvoltage Quick service center
5 Extended output overload Check battery bank and loads
6 Both fans blocked Quick service center
9 Two chargers in a group with the same priority Check group and priority with the RDS 1562
10 Both internal temperature sensors faulty Quick service center
11 BULK phase over 8 hours (default) Check batteries and loads
12 ABSORPTION phase over 24 hours (default); output held at FLOAT Check batteries and loads
  • Manual reset: remove the cause, disconnect AC for 10 seconds, reconnect.
  • Automatic-reset problems (red ERROR LED): over temperature, blocked fan, AC low (below 207 Vac HR / 108 Vac FR: output limited to 70%), AC fail (below 161 Vac HR / 83 Vac FR), cold battery (< –15°C), hot battery (> +50°C), sensor fault, CAN error.
  • Maintenance: none; check cables and connections once a year.