INSTALLATION MANUAL

Installation, wiring, LED signals and technical data for the Quick VRS 30 switching voltage reducer (24 V in, 13,5 V out, 30 A).

DocumentQuick VRS 30 HE Voltage Reducer Installation Manual
FormatPDF · 28 pages · 0.3 MB
LanguageEnglish
Quick VRS 30 HE Voltage Reducer — Installation Manual

Technical Data

Item VRS 30
Maximum output current (1) 25 A
Maximum output load (2) 30 A
Rated output voltage 13,5 Vdc, stability 1%
Residual fluctuation 50mV max
Supply voltage 20 ÷ 30 Vdc
Maximum absorption 22,2 A
Operating temperature from –20 to + 40° C
Cooling / humidity Natural / max. 95% RV without condensation
Efficiency 85%
EMC EN 55022-B
Case Aluminium, 189 x 254 x 68 mm, 1,7 Kg
  • Protections: reverse input polarity (through fuse), reverse output polarity (through diode), overload, output short circuit, output overvoltage (through zener diode), overheating; battery protection against excessive discharge.
  • (1) Continuous operation. (2) Intermittent: 1 min on, 1 min off at 20 °C ambient.

Location & Sizing

  • Fixed indoor installation in a dry, ventilated place; horizontal or vertical with cables exiting downwards (vertical recommended for cooling).
  • At least 5 cm between the unit (except its base) and walls or objects; the base must withstand 80°C (at 40°C ambient). The case is the heat sink and can get very hot.
  • Battery 24 V, recommended capacity >120 Ah; minimum output cable 10 mm2 (size for the run length); insulated female Faston 6,3 x 0,8 terminals.
  • Output fuse: the English table gives 30 A FAST, the German table 6 A FAST (x3) (as printed); check your unit's label.

Wiring & Use

  • 24 V battery to IN, 12 V equipment to OUT through the fuse (Fig. 1); check input and output polarity, cables not live while connecting.
  • Undersized cables or poor joints can overheat dangerously. Wire to local electrical codes.
  • POWER switch turns the unit on and off. In a fault the output is cut and restored automatically once conditions are normal (no overload, temperature and battery voltage correct).
  • Maintenance: none; check cables and connections once a year. Opening by unauthorised personnel voids the warranty.
LED Colour Meaning
OUT Off No output voltage: unit off or in protection
OUT Green Power on
TEST Off Unit off
TEST Green No faults during operation
TEST Red Protection for over temperature or low input voltage: check output wiring and loads, installation and the input battery bank

TEST red with OUT green means a fault occurred and has cleared: switch the unit off and on again.