INSTRUCTIONS

Trip ratings, assembly sequence, wiring and dimensions for the Quick WCB hydraulic-magnetic DC circuit breaker used to protect and isolate a windlass.

DocumentQuick WCB Hydraulic Magnetic Circuit Breaker Installation Instructions
FormatPDF · 2 pages · 0.2 MB
LanguageEnglish
Quick WCB Hydraulic Magnetic Circuit Breaker — Installation Instructions

Models and Ratings

A DC-specific overcurrent protection: it trips on overcurrent and is reset by hand.

Model Trip current Operating voltage Operating temperature
WCB 40 40 A Max. 80 Vdc −40°C to +85°C
WCB 50 50 A Max. 80 Vdc −40°C to +85°C
WCB 60 60 A Max. 80 Vdc −40°C to +85°C
WCB 80 80 A Max. 80 Vdc −40°C to +85°C
WCB 100 100 A Max. 80 Vdc −40°C to +85°C

Operating temperature refers to the hydraulic-magnetic breaker. Dimensions: plate 49,8 × 74,8 mm (1 61/64 × 2 15/16"); depth behind the panel 67 mm (2 41/64"); toggle 30,4 mm (1 13/64") proud.

Assembly

Quick WCB circuit breaker exploded assembly drawing

No. Part
1 Hydraulic-magnet (breaker)
2 Plastic washer
3 Neoprene gasket
4 Control plate
5 4 self-tapping screws
6 Anti-rotation screw
7 WCB label
8 Red magnetic-hydraulic protective cap
  • Assemble in the numbered order.
  • 7a: peel the backing from the label without touching the adhesive, after cleaning the control plate (4). Do not apply below 18 °C.
  • 7b: lay one side of the label against the edge of the control plate first, then press the whole surface down firmly.
  • 7c: remove the transparent protective film.

Item 8 is a red protective cap in the English list but a black diverter cap in the Italian list (as printed).

Wiring

  • The breaker sits in the positive lead: LINE terminal to the battery (or DC supply) positive, the other terminal to the positive of the equipment; battery negative straight to the equipment negative.
  • Maximum 80 Vdc.