OWNER'S MANUAL

How the Sleipner ESI-1 turns 4-20mA autopilot or third-party signals into proportional bow and stern thrust on S-Link: inputs and outputs, DIP switches, activation and priority modes, specifications, dimensions and wiring.

DocumentSleipner External Signal Interface ESI-1 Installation & User Manual
FormatPDF · 12 pages · 1.0 MB
LanguageEnglish
Sleipner External Signal Interface ESI-1 — Installation & User Manual

What It Does

  • External Signal Interface to the S-Link bus with two 4-20mA analogue inputs that control bow (AI1) and stern (AI2) thrusters proportionally.
  • Operates all E, SEP, SH and SAC series thrusters, including retractable thrusters and the Automatic Main Switch; typically used with autopilots with 4-20mA outputs and third-party control systems.
  • 12mA = centre, thruster stopped (dead band 11.6mA to 12.4mA); 4mA = 100% port (from 4.4mA), 20mA = 100% starboard (from 19.6mA).
  • DI1 (12V or 24V) enables AI1/AI2 and closes relay RO1 as activation feedback. RO2 is run-enable feedback for hydraulic thrusters with PHC controllers and opens on PHC emergency feedback.

Settings

  • DIP switches 3 and 4 set the operation mode and must be OFF.
  • DIP switch 1 OFF (default): any other device sending thrust overrides the ESI-1, which resumes 3 seconds after the last command. ON: same priority as other devices; the controller outputs the highest thrust and stops on conflicting directions.
  • DI1 functionality (S-Link Programmer): Always ON (default) or Pulse Activation – a pulse of minimum 100ms toggles activation; it deactivates after 60 minutes with inputs centred at 12mA (or one centred and one out of range).
  • Priority Mode 0 (default): same S-Link priority as all devices. Mode 1: ESI-1 is deactivated whenever a PJC panel is active (PJC2xx panels need the ESI-1 Priority Mode 1 upgrade).
  • Green status LED: continuous = power and S-Link OK; flashing = power OK, no S-Link communication.

Technical Specifications

Item Value
Supply 8-31 VDC / max 7 Watts
Operating temperature –20°C to +70°C [–4°F to +158°F]
Storage temperature –40°C to +85°C [–40°F to +176°F]
IP rating IP20
Weight 500 g [1.1 lb]
Digital inputs DI1 to DI7 Opto-isolated 8-31V, common 0V
Digital outputs DO1 to DO6 Max 4A, dedicated supply 8-31VDC
Relay contacts (NO) RO1–RO4 Max. switching current 10A at 24VDC
Analogue inputs AI1 & AI2 4-20mA, non isolated, resistive load (the source supplies loop power)
Analogue outputs AO1 & AO2 4-20mA, isolated, external loop power required
Temp sensors T1 KTY84 1K ohm @ 100°C; T2 NTC 100K ohm @ 25°C
Terminals 0.2 to 1.5 mm² [16 to 24 AWG] cage clamp

Dimensions

Code Measurement mm inch
L Length 190 7.48
+L Additional length 212 8.35
H Height 156.5 6.16
W Width 58.5 2.3
+W Additional width 2,8 0.11
(a) Fixing holes, width 200 7.87
(b) Fixing holes, height 95 3.74

Screw the unit to a solid surface. Power it externally (8-31V DC) through a 5A breaker/fuse, and connect it to S-Link for the thruster controllers. DI1 needs a signal ground on the DI_GND terminal.

Connection Summary

Terminal Use
+24V / 0V Supply via 5A breaker/fuse
DI1 / DI_GND Thrust enable (12V or 24V)
AI1+ / AI1- Bow thrust 4-20mA (loop supply from the source)
AI2+ / AI2- Stern thrust 4-20mA (loop supply from the source)
RO1A / RO1C Thrust enable feedback
RO2A / RO2C Run enable feedback (hydraulic)
S-Link Power cable #6 1328, terminator #6 1327 on the backbone
  • S-Link is CAN-based: BACKBONE cables (blue connectors) carry power and data, one SPUR cable (green connectors) per connected unit, T-connectors or 4-port T-connectors to join them, BACKBONE Extenders to lengthen.
  • One POWER cable per system, ideally mid-backbone, with a 2A fuse: yellow and black to GND, red to +12VDC or +24VDC.
  • An END Terminator at each end of the backbone. Spare spurs may stay unterminated but protect the open connectors from water.
  • Avoid sharp bends, close the connector locks fully, keep cables out of standing water and away from radio transmitters, antennas and high-voltage cables.
  • Only original Sleipner S-Link products or approved Sleipner interfaces on the bus; with third-party control at least one original Sleipner panel must be installed.