| No. / group |
Parameter |
Options and default |
| 01 Device |
Instance |
NONE (mono hull, default); PORT / STARBOARD for catamarans with two PHC-3 |
| 01 Device |
Thruster config |
BOW/STERN (default), BOW/BOW or STERN/STERN (both valves as one thruster) |
| 01 Device |
Pump2 output |
AUTOMATIC (default): second PTO pump shut down when not needed, woken for 15 minutes if stabilizer pressure drops 30% below set-point; or ALWAYS ON / DEACTIVATED |
| 01 Device |
System pressure |
ANALOG INPUT 0-400bar 4-20mA (default), SWITCH INPUT or deactivated |
| 02 Tank monitor |
Sensor type |
AN-LEVEL/AN-TEMP 0-180ohm + NTC 10K, part no. 10 2543 (default); NO-LEVEL/AN-TEMP (10 2540 & 10 2542); NC-LEVEL/NC-TEMP; deactivated |
| 02 Tank monitor |
Oil alarm level / tank height / oil level 100% |
65% (steps of 5%) / 350mm (300mm – 15000mm) / 270mm (150mm – 15000mm), measured from the tank centre if the bottom is not flat |
| 03 Cooling pump |
Pump type / mode |
D-OUT 4 blue harness (default), hydraulic grey harness, electric ECI or CC Module; TEMP CONTROLLED (default), ALWAYS ON or deactivated |
| 03 Cooling pump |
ECI speed / power save / trim |
1400rpm (800rpm – 1600rpm); power save stops the pump after 10 seconds with no pressure and the power pack idle; trim runs it 30 seconds after power-up, whenever pressure is applied and every 6 days |
| 05 Digital outputs |
D-OUTPUT 1–6 |
+24V, max 2.0A each; functions include bow/stern crossover (with or without brake), cooling pump, thrust active, thruster enabled, low oil alarm, active fault, system pressure available; a negative number inverts the output |
| 06 Digital inputs |
D-INPUT 1, 2, 4 |
Start power pack, pressure / return filter warning (after 5 seconds), E-stop bow / stern, start aux pressure; 15 minute time-out on power-pack starts |
| 10 Power pack |
Config / set-point |
NONE (default), PTO and VFD(AC), PTO ONLY, VFD(AC) ONLY; pressure set-point 70bar default; reduced power 70%; pressure sensor range 160bar; PTO over-pressure fault 130bar |
| 10 Power pack |
VFD |
ABB ACS580 (default), ABB ACS550, VACON NX or EHP (eVision Hydraulic Powerpack, on S-Link); Modbus 57600,8,EVEN,1 default; min / max speed 200rpm / 1500rpm |
| 20 / 21 Thrusters |
Valve, direction, spool travel |
Danfoss PVG (default); NORMAL or SWAPPED direction (instead of swapping hoses); max spool travel 100% (50% - 100%) |
| 20 / 21 Thrusters |
Ramps / direction lock |
Ramp increase and decrease 200ms (100ms – 10000ms); direction lock 1000ms |
| 20 / 21 Thrusters |
Crossover |
Must be enabled on all 412mm (16inch), 513mm (20inch) and 610mm (24inch) tunnel thrusters (bypass/crossover valve); enabling sets ramp decrease to 3000ms |
| 20 / 21 Thrusters |
Function / asymmetric thrust |
NORMAL tunnel or SRHP retract (auto-detected); asymmetric thrust 0 – 100% for dual installations (catamarans, stern drives) |