OWNER'S MANUAL

Operation, seasonal maintenance and troubleshooting from the Sleipner Side-Power SEP & SEP-IP user manual, plus specifications, dimensions, torque values and cable/fuse sizing from the SE Pro (SEP20 to SEP300) installation guides.

Sleipner SE Pro (SEP) DC Electric Thrusters — Installation & User Manual

This manual is split into 2 pages: Part 1 → · Part 2

Electrical Reference Guide

  • Components: battery, fuse, main switch, PPC (proportional models) and motor. Fuse and main switch as close as possible to the positive battery terminal; main switch easy to reach. Dual thrusters on one bank: a fuse and main switch per thruster; dual thrusters on two banks need a common ground (OST guide).
  • Automatic Main Switch: follows the control panel on/off, needs its own fused supply and the right voltage rating.
  • Gasoline engine spaces or areas exposed to explosive gases: use ignition-protected products (ISO 8846, SAE J1171 or UL 1500).
  • Lugs back to back, no washers between lugs, spring washer outermost. After wiring, check with an ohmmeter (main switch off) that neither motor terminal connects to the motor flange.
Model Volt Nominal current Min. battery CCA Rec. fuse <7 m
min / rec.
7–14 m
min / rec.
15–21 m
min / rec.
22–28 m
min / rec.
28–35 m
min / rec.
36–45 m
min / rec.
20/110S 12V 150 A DIN: 200
SAE: 380
EN: 330
ANL 150 25 / 35 mm²
3 / 2 AWG
35 / 50 mm²
2 / 1/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 95 mm²
3/0 / 3/0 AWG
120 / 2×70 mm²
2×4/0 / 2×2/0 AWG
25/110S 12V 200 A DIN: 200
SAE: 380
EN: 330
ANL 150 25 / 35 mm²
3 / 2 AWG
50 / 50 mm²
1/0 / 1/0 AWG
70 / 70 mm²
2/0 / 2/0 AWG
95 / 95 mm²
3/0 / 3/0 AWG
120 / 120 mm²
4/0 / 4/0 AWG
2×70 / 2×70 mm²
2×2/0 / 2×2/0 AWG
30/125S / 30/140 12V 245 A DIN: 200
SAE: 380
EN: 330
ANL 150 35 / 50 mm²
2 / 1/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×70 / 2×95 mm²
2×2/0 / 2×3/0 AWG
40/125S / 40/140 12V 315 A DIN: 300
SAE: 570
EN: 520
ANL 250 35 / 50 mm²
2 / 1/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×95 / 2×95 mm²
2×3/0 / 2×3/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
50/140S 12V 370 A DIN: 350
SAE: 665
EN: 600
ANL 325 50 / 50 mm²
1/0 / 1/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×70 / 2×95 mm²
2×2/0 / 2×3/0 AWG
2×95 / 2×120 mm²
2×3/0 / 2×4/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
50/140S 24V 170 A DIN: 175
SAE: 332
EN: 280
ANL 150 25 / 25 mm²
3 / 3 AWG
25 / 35 mm²
3 / 2 AWG
35 / 50 mm²
2 / 1/0 AWG
35 / 50 mm²
2 / 1/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 70 mm²
2/0 / 2/0 AWG
60/185S / 60/140 12V 370 A DIN: 350
SAE: 665
EN: 600
ANL 325 50 / 50 mm²
1/0 / 1/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×70 / 2×95 mm²
2×2/0 / 2×3/0 AWG
2×95 / 2×120 mm²
2×3/0 / 2×4/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
60/185S / 60/140 24V 170 A DIN: 175
SAE: 332
EN: 280
ANL 150 25 / 25 mm²
3 / 3 AWG
25 / 35 mm²
3 / 2 AWG
35 / 50 mm²
2 / 1/0 AWG
35 / 50 mm²
2 / 1/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 70 mm²
2/0 / 2/0 AWG
80/185T 12V 530 A DIN: 550
SAE: 1045
EN: 940
ANL 400 70 / 70 mm²
2/0 / 2/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×95 / 2×95 mm²
2×3/0 / 2×3/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
2×120 / NA mm²
2×4/0 / AWG
NA
80/185T 24V 280 A DIN: 300
SAE: 570
EN: 520
ANL 250 35 / 35 mm²
2 / 2 AWG
35 / 50 mm²
2 / 1/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×95 mm²
4/0 / 2×3/0 AWG
100/185T 12V 740 A DIN: 750
SAE: 1425
EN: 1320
ANL 500 95 / 95 mm²
3/0 / 3/0 AWG
2×70 / 2×95 mm²
2×2/0 / 2×3/0 AWG
2×120 / NA mm²
2×4/0 / AWG
NA NA NA
100/185T 24V 340 A DIN: 400
SAE: 760
EN: 680
ANL 325 50 / 50 mm²
1/0 / 1/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×95 mm²
4/0 / 2×3/0 AWG
2×95 / 2×120 mm²
2×3/0 / 2×4/0 AWG
120/215T 24V 420 A DIN: 450
SAE: 855
EN: 760
ANL 325 70 / 70 mm²
2/0 / 2/0 AWG
70 / 70 mm²
2/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×70 / 2×95 mm²
2×2/0 / 2×3/0 AWG
130/250T 12V 800 A DIN: 750
SAE: 1425
EN: 1320
ANL 500 95 / 95 mm²
3/0 / 3/0 AWG
2×95 / 2×95 mm²
2×2/0 / 2×3/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
NA NA NA
130/250T 24V 350 A DIN: 400
SAE: 760
EN: 680
ANL 325 50 / 50 mm²
2 / 1/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×95 / 2×95 mm²
2×3/0 / 2×3/0 AWG
150/215T 24V 610 A DIN: 560
SAE: 1064
EN: 940
ANL 500 70 / 70 mm²
2/0 / 2/0 AWG
95 / 95 mm²
3/0 / 3/0 AWG
120 / 120 mm²
4/0 / 4/0 AWG
2×70 / 2×95 mm²
2×2/0 / 2×3/0 AWG
2×95 / 2×120 mm²
2×3/0 / 2×4/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
170/250TC 24V 550 A DIN: 560
SAE: 1064
EN: 940
ANL 400 70 / 70 mm²
2/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×95 mm²
4/0 / 2×3/0 AWG
2×95 / 2×95 mm²
2×3/0 / 2×3/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
210/250TC 24V 500 A DIN: 560
SAE: 1064
EN: 940
ANL 400 70 / 70 mm²
2/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×70 mm²
4/0 / 2×2/0 AWG
2×70 / 2×95 mm²
2×2/0 / 2×3/0 AWG
2×95 / 2×120 mm²
2×3/0 / 2×4/0 AWG
250/300TC 24V 610-670 A DIN: 700
SAE: 1330
EN: 1170
ANL 500 70 / 70 mm²
2/0 / 2/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 2×95 mm²
4/0 / 2×3/0 AWG
2×95 / 2×95 mm²
2×3/0 / 2×3/0 AWG
2×95 / 2×120 mm²
2×3/0 / 2×4/0 AWG
2×120 / 2×120 mm²
2×4/0 / 2×4/0 AWG
300/300TC 48V 400-450A DIN: 400
SAE: 760
EN: 680
ANL 325 50 / 70 mm²
1/0 / 2/0 AWG
50 / 70 mm²
1/0 / 2/0 AWG
70 / 95 mm²
2/0 / 3/0 AWG
95 / 120 mm²
3/0 / 4/0 AWG
120 / 120 mm²
4/0 / 4/0 AWG
2×95 / 2×120 mm²
2×3/0 / 2×4/0 AWG

Total cable length = positive plus negative. NA = not applicable at that length. The 20/110S row gives "2 x 4/0" minimum and "2 x 2/0" recommended AWG at 36–45 m (as printed). The 150/215T AWG row is labelled "2" instead of "AWG" (as printed).

SE to SEP Upgrade (Kit 8 1998 / 8 1999)

  • Converts an SE motor to proportional (SEP) control with a new motor loom and temperature sensor; the control box is fitted on motors from 1999 onwards.
  • Cut the red wire to the old control box so the connections to the two positive solenoid coil terminals and the main positive terminal remain; isolate any redundant wires left protruding from the motor.
  • Fit the temperature sensor to the brush holder without touching the motor housing. Grey and blue to the solenoid coils in the same positions as the old loom, white to A2; the multi cable goes to the PPC.
Kit Description
8 1999 Kit 8 1999 – SE to SEP modification View part →

Post-Installation Checklist

  • Gear leg / motor bracket bolts and motor bolts tightened correctly.
  • All electrical connections clean, dry and tight; correct cable, fuse and main switch size.
  • With an ohmmeter (main switch off): no connection between the motor body/flange and the positive terminal, nor between the motor body and the negative terminal.
  • Anti-fouling on gear leg and propeller, but NOT on anodes, sealing/rubber fittings or propeller shafts.
  • Propeller fastened correctly and turning freely in the tunnel; anode and/or holding screw tight with thread glue.
  • No water leakage round the installation; drive direction matches the control panel; user manual handed to the owner.

Warranty: two years for leisure use, one year for commercial and other non-leisure use, from delivery to the end user (dealer and builder grace periods apply). Wearable/service parts are not covered, and skipping the maintenance described in the manuals voids the warranty on the affected parts.

Need a part that isn't listed? Ask us to source it and quote the part number from the PDF.